Without Heat Shield
With Heat Shield
Cat No. Description
0485H05 Canister 0.5 Liter with Heat Shield
0485H10 Canister 1.0 Liter with Heat Shield
0485H15 Canister 1.5 Liter with Heat Shield
0485H20 Canister 2.0 Liter with Heat Shield
0485H30 Canister 3.0 Liter with Heat Shield
0485H40 Canister 4.0 Liter with Heat Shield
Cat No.
Description
0485005 Canister 0.5 Liter
0485010 Canister 1.0 Liter
0485015 Canister 1.5 Liter
0485020 Canister 2.0 Liter
0485030 Canister 3.0 Liter
0485040 Canister 4.0 Liter
Cat. No. 0485 Series
Marine Evaporative Emissions Carbon Canister
Installation Instructions
Note: Failing to follow these instructions when installing the evaporative emissions canister in a piece of nonroad equipment
violates federal law (40 CFR 1068.105(b)), subject to fines or other penalties as described in the Clean Air Act.
Location
The canister can be mounted in any location that the current vent line is located. The canister is installed between the
fuel tank vent fitting and the fresh air vent fitting. The canister must be mounted above the highest point of the fuel tank.
Thought must be given to the following when choosing a location:
The hose connections to the canister must be accessible for inspection and service.
The canister should not be mounted in a location where it will be stepped on or otherwise have a force exerted
upon it.
The canister is designed to withstand a temperature range from -40° C to 80° C.
The canister can be mounted in any orientation
If mounted in the engine compartment, the canister must have a heat shield (this is an optional component that
will be integral to the canister).
System Requirements
The fuel tank vent system must be designed in such a way that liquid fuel is not passed through the vent line and into the
canister. The vent system must also prevent the intake of water into the vent system and into the canister. These are
requirements of the EPA regulation. When designing your fuel system you must also consider fuel expansion and
situations such as storage of the vessel with a full tank on an incline.
Mounting of the Canister
The canister (with the bracket) is designed to be mounted with (4) #10 flat head or oval head screws. This is the setup
that has been validated to ABYC standards. If the installer chooses to mount the canister in some other fashion (not using
the end brackets), they are responsible for the validation of the mounting. Please note that the canister has an internal
plate and spring that must be able to move inside the body of the canister. For this reason any mounting mechanism
must not constrict the body for 50 mm (2 inches) from either end of the canister body.
Connection of the Vent Line to the Canister
The vent hose must be anchored to the boat structure within 6 inches of the canister fittings. The vent hose must be
routed to prevent a load from being exerted onto the canister fittings.
Hose clamps must used in accordance with ABYC Fuel System Vent Hose Clamping Standards (H24 Table 3). The clamp
must not distort the fitting on the canister when tightened.
PERKO, INC.
16490 N.W. 13th Avenue
4/11 Miami, FL 33169-5707
0485INS1 www.perko.com